yeah used to manage data centers, diesel breaks down after a while, petrol even faster.
you can put in additives to extend the life, and specialized storage can squeak even more out, but ultimately you can't plan on it being good past 12 months, maybe as low as 5-6 if conditions aren't great.
we ran / tested the generators weekly, both just to exercise them and confirm they're good, but also just to burn off old fuel.
you can put in additives to extend the life, and specialized storage can squeak even more out, but ultimately you can't plan on it being good past 12 months, maybe as low as 5-6 if conditions aren't great.
we ran / tested the generators weekly, both just to exercise them and confirm they're good, but also just to burn off old fuel.